KM-2-16000-T/hs-Kolvi-4000

Description

Transportable block-modular boiler house KM-2-16000-T/hs-KOLVI-4000

Technical characteristics

Parameter name Unit of measurement Meaning
Rated installed heat output of the boiler equipment kW 16000
Overall dimensions of one container for transportation (excluding detached external equipment), length × width × height mm 9000х2500х4000
Overall dimensions of the boiler house (excluding detached external equipment), length × width × height mm 9000х17500х4000
Internal volume of the boiler house, not less than м3 563
Fire hazard category of the boiler house container Г
Fire resistance rating of the boiler house container ІІІа
Installed boiler equipment, name — quantity units KOLVI 4000 boiler — 4 units
Required minimum gas pressure upstream of the burner multiblock valves mbar 225
Permissible gas pressure upstream of the burner multiblock valves, within the range mbar 225…500
Rated gas consumption (at Qₙ = 8200 kcal/m³) m³/h 1804,14
Minimum gas consumption (at Qₙ = 8200 kcal/m³) m³/h 73,41
EFFICIENCY % 93
Maximum operating coolant pressure MPa 0,6
Maximum coolant temperature оС 115
Minimum coolant temperature in the return pipeline оС 55
Minimum temperature of combustion products оС 160
Maximum coolant flow rate at Δt = 20 °C m³/h 344
Concentration of harmful substances in combustion products — CO, not more than mg/m³ 60
Concentration of harmful substances in combustion products — NOx (calculated as NO₂), not more than mg/m³ 130
Power supply voltage of the electrical equipment V ~380/~220
Electrical power of the current consumers in operating mode, not more than kW 138,0
Boiler house weight, not more than t 98