Boiler KTN 100 SE A
Description
The KTN 100 SE A boiler is designed for heat supply of larger facilities (residential buildings, apartments, municipal buildings) with water heating systems. Operating pressure - up to 0.3 MPa (3 bar), maximum water temperature - up to 80°C. It has an open combustion chamber (type B11BS), two 48 kW heat exchangers in a single housing and two chimneys for natural exhaust of combustion products. It is equipped with draught stabilizers, a gas exhaust control system, gas burners with SIT automation and safety devices. Depends on power supply, supports weather-dependent and cascade control.
Technical characteristics
| Parameter name | Unit of measurement | Meaning. |
|---|---|---|
| Fuel | Natural gas (33500-36000 kJ/m³) | |
| Rated heat output | kW | 96 |
| Maximum outlet water temperature | °C | 80 |
| Nominal gas pressure | Pa. | 1960 (20 mbar) |
| Pressure in the heating system, not more than | bar | 3 |
| Diameter of connection pipes: heating circuit | inch | G1½ (2 pcs.) |
| Diameter of the flue gas outlet | mm | 158 (2 pcs.) |
| Dimensions: height | mm | 1161 |
| Dimensions: width | mm | 1326 |
| Dimensions: depth | mm | 700 |
| Weight of the device | kg | 328 |
Customers who have chosen KOLVI