Description
Transportable modular boiler house KM-2-600-T/hn-VPM-192DN(TN)
Technical characteristics
| Parameter name | Unit of measurement | Meaning |
|---|---|---|
| Rated installed heat output of the boiler equipment | kW | 576 |
| Minimum heat output of the boiler equipment | kW | 45 |
| Overall dimensions of one container for transportation (excluding detached external equipment), length × width × height | mm | 6000х2500х2650 |
| Internal volume of the boiler house, not less than | м3 | 39 |
| Fire hazard category of the boiler house container | Г | |
| Fire resistance rating of the boiler house container | ІІІа | |
| Installed boiler equipment, name — quantity | units | VPM-192DN(TN) modular instantaneous water heater — 3 units |
| Required gas pressure upstream of the burner multiblock valves | mm H₂O | 200 |
| Rated gas consumption (at Qₙ = 8200 kcal/m³) | m³/h | 65,66 |
| Minimum gas consumption (at Qₙ = 8200 kcal/m³) | m³/h | 5,07 |
| EFFICIENCY | % | 92 |
| Maximum operating coolant pressure | MPa | 0,3 |
| Maximum coolant temperature | оС | 80 |
| Minimum temperature of combustion products | оС | 110 |
| Maximum coolant flow rate at Δt = 20 °C | m³/h | 24,8 |
| Concentration of harmful substances in combustion products — CO, not more than | mg/m³ | 20 |
| Concentration of harmful substances in combustion products — NOx (calculated as NO₂), not more than | mg/m³ | 20 |
| Power supply voltage of the electrical equipment | V | ~380/~220 |
| Electrical power of the current consumers in operating mode, not more than | kW | 8,5 |
| Boiler house weight, not more than | t | 5,0 |