Boiler KTN 100 SE A

Description

The KTN 100 SE A boiler is designed for heat supply of larger facilities (residential buildings, apartments, municipal buildings) with water heating systems. Operating pressure - up to 0.3 MPa (3 bar), maximum water temperature - up to 80°C. It has an open combustion chamber (type B11BS), two 48 kW heat exchangers in a single housing and two chimneys for natural exhaust of combustion products. It is equipped with draught stabilizers, a gas exhaust control system, gas burners with SIT automation and safety devices. Depends on power supply, supports weather-dependent and cascade control.

Technical characteristics

Parameter name Unit of measurement Meaning.
Fuel Natural gas (33500-36000 kJ/m³)
Rated heat output kW 96
Maximum outlet water temperature °C 80
Nominal gas pressure Pa. 1960 (20 mbar)
Pressure in the heating system, not more than bar 3
Diameter of connection pipes: heating circuit inch G1½ (2 pcs.)
Diameter of the flue gas outlet mm 158 (2 pcs.)
Dimensions: height mm 1161
Dimensions: width mm 1326
Dimensions: depth mm 700
Weight of the device kg 328