Block-type gas boiler houses

for heat supply of buildings and structures

In KM-2 type block-modular gas boiler houses, the heat-generating equipment consists of Kolvi steel fire-tube hot-water boilers fitted with fan burners, in which combustion air is supplied under forced draft.

These boiler houses are used for the heat supply of buildings whose specifications require maintaining a heating system temperature schedule of 90/70 °C or higher, with high coolant pressure (above 0.3 MPa at the boiler house inlet).

Block-type gas boiler houses belong to the category of high-capacity boiler installations (up to 69 MW) that cannot be manufactured as transportable containers due to their large overall dimensions. 

Such boiler houses are manufactured in the form of technological blocks and assemblies that are transported and assembled at the installation site. Under factory conditions, the boiler house is divided into blocks in such a way that assembling the unified structure during installation work takes minimal time.

The main model range of Kolvi KM-2 block-modular boiler houses

  1. KM-2-12000-B/hs-Kolvi 6000T
  2. KM-2-15000-B/hs-Kolvi 5000T
  3. KM-2-12000-B/hs-Kolvi 6000T
  4. KM-2-24000-B/hs-Kolvi 8000T
  5. KM-2-28000-B/hs-Kolvi 14000T
  6. KM-2-34000-B/hs-Kolvi 17000T
  7. KM-2-42000-B/hs-Kolvi 14000T
  8. KM-2-51000-B/hs-Kolvi 17000T
  9. KM-2-69000-B/hs-Kolvi 23000T

Technical characteristics

Parameter name KOLVI 5000T KOLVI 10 000T
Rated heat output, kW 5000 10000
Maximum operating pressure of the boiler, MPa (bar) 1,0 (10) 1,0 (10)
Fuel consumption
Natural gas, m³/h 569,9 1139,8
Diesel fuel, kg/h 444,4 888,8
Max. outlet boiler water temperature, °C 115 115
Minimum coolant pressure, bar 1,5 1,5
Water volume in the boiler, L 8561 19733
Efficiency, not less than, % 92 92
Boiler furnace resistance on the flue gas side, mbar 8,2 8,7
Hydraulic resistance of the water circuit, mbar 180 180
Connection pipe diameters
Supply/return DN/PN 200 300
Safety valve, DN/PN 80 100
Drain, DN/PN 40 40
Flue diameter, mm 600 900
Boiler dimensions excluding the burner
Length, not more than, mm 5550 7320
Width, not more than, mm 2260 2910
Height (including nozzle), not more than 2660 3360
Boiler weight, kg 12750 24630
Warranty period (from the date of commissioning), years 2 2
Emissions when burning natural gas, mg/m³
CO, not more than 30 30
NOx, not more than 130 130